VAE-660
The VAE-660 is a six-phase protection relay test system providing 6×0–30 A AC current, 6×0–120 V AC voltage…
- Current output 6×0–30 A AC
- Single-phase current 1×0–180 A
- Voltage output 6×0–120 V AC / 3×0–240 V
CT/PT Analyzer
All-in-one instrument-transformer analyzer for protection CTs, measuring CTs, TP-class CTs and inductive PTs — knee-point up to 40 kV.
| Specification | Value | Unit |
|---|---|---|
| Test standards | IEC 61869-2 (IEC 60044-1, 60044-6) · IEC 61869-3 (IEC 60044-2) · IEEE/ANSI C57.13 | |
| Max. knee-point voltage | 40 | kV |
| Measurement principle | Low-frequency excitation / voltage method | |
| Platform | DSP + ARM, embedded Linux | |
| Display | 5.7″ LCD | |
| Operation | Multi-function rotary mouse · local or PC remote | |
| Output voltage | 0 – 180 | V RMS |
| Output current | 0 – 12 (RMS) · 36 (peak) | A |
| Voltage measurement accuracy | ±0.05 % | |
| CT ratio range / accuracy | 1 – 30000 / ±0.05 % | |
| PT ratio range / accuracy | 1 – 10000 / ±0.05 % | |
| Phase accuracy / resolution | ±2 min / 0.01 min | |
| Secondary winding resistance | 0 – 300 Ω · accuracy 0.1 % ±1 mΩ | |
| Burden | 0 – 300 VA · accuracy 0.1 % ±0.1 VA | |
| Memory | > 3000 test-result groups | |
| Nominal input voltage | AC 230 V / 120 V ±10 % (customized), 1-phase | |
| Nominal frequency | 50 / 60 | Hz |
| Rated current | 10 A at 230 V · 12 A at 120 V | |
| Connection | Standard AC socket (IEC 60320) | |
| Operating temperature | 0 … +50 | °C |
| Storage temperature | −25 … +70 | °C |
| Humidity | 5 … 95 % RH, non-condensing | |
| Vibration | IEC 60068-2-6 (20 m/s² at 10–150 Hz) | |
| Weight | 9 | kg |
| Dimensions (W×H×D, without handle) | 340 × 300 × 150 | mm |
| Connection ports | 2 × USB 2.0 · 1 communication port | |
Protection CTs, measuring CTs, TP-class CTs and inductive PTs per IEC 61869-2/-3 and IEEE/ANSI C57.13.
Low-frequency excitation derives high-equivalence knee-point voltages (up to 40 kV) without a large external HV source.
Voltage-method ratio, polarity, ratio-error and phase-displacement measurement with ±0.05 % accuracy.
Complete test routine finishes in seconds with a single click of the patented multi-function rotary mouse.
Measures 0–300 Ω winding resistance and 0–300 VA burden with 0.1 % accuracy.
Embedded Linux platform with 5.7″ LCD for stand-alone use, plus remote PC control.
Print test reports directly in the field; store >3000 result groups on board.
Only 9 kg (19.84 lb) in a 340×300×150 mm case.
Acceptance, routine and diagnostic testing of current and voltage transformers on-site.
Excitation, ratio, polarity, error curve, resistance and burden tests for all CT classes.
Transient-protection CT characterization for modern distance and differential protection.
Production-line and factory acceptance testing in instrument-transformer plants.
Reference-standard testing and certification of CT/PT units.
Protection CTs, measuring CTs, TP-class CTs and inductive PTs (voltage transformers), covering ratio, polarity, excitation characteristic, error curve, secondary resistance and burden — per IEC 61869-2/-3 and IEEE/ANSI C57.13.
No. The analyzer uses a low-frequency excitation principle, so very high equivalent excitation voltages (up to 40 kV knee point) are derived from a low-power 0–180 V / 0–12 A output without a large external high-voltage supply. This makes on-site high-knee-point testing practical and safe.
Yes — a built-in thermal printer prints test results directly, and more than 3000 result groups can be stored internally for later transfer by USB.