30 kV Very Low Frequency (VLF) AC Hipot Test Set
Lightweight two-piece 30 kV peak VLF hipot for routine and maintenance withstand testing of shielded power cables.
| Specification | Value | Unit |
|---|---|---|
| Output AC voltage (peak, sinusoidal) | 0 – 30 | kV |
| Output current (peak) | 0 – 30 | mA |
| Output frequency | 0.1 / 0.05 / 0.02 / 0.01 | Hz sinusoidal |
| Duty cycle | Continuous | |
| @ 0.1 Hz | ≤ 0.5 | µF |
| @ 0.05 Hz | ≤ 1.1 | µF |
| @ 0.02 Hz | ≤ 2.2 | µF |
| @ 0.01 Hz | ≤ 5.5 | µF |
| Measurement accuracy | ± 3 % of reading | |
| Voltage positive / negative peak error | ≤ 3 % | |
| Controller unit weight | 4 | kg |
| High-voltage tank (booster) weight | 20 | kg |
| Design | Two-piece split system (controller + HV tank) | |
| Power supply | AC 220 V / AC 230 V, 50/60 Hz, or AC 120 V, 60 Hz | |
| Operating temperature | −10 … +50 | °C |
| Storage temperature | −20 … +70 | °C |
| Humidity | ≤ 85 % RH | |
Control unit of 4 kg plus a 30 kV high-voltage tank of 20 kg — one of the lightest split systems in the family, easily handled by two technicians.
Polarity reverses every half cycle like power-frequency AC, giving a space-charge-free stress appropriate for XLPE and EPR insulation.
0.1 / 0.05 / 0.02 / 0.01 Hz let the operator trade test time for reach on high-capacitance cable sections.
Delivers full rated voltage across the load rating up to 5.5 µF at 0.01 Hz on a continuous duty cycle.
The 7-inch touch-screen controller judges results against IEEE 400.2 criteria automatically.
Results are saved internally and printed on site, producing field documentation without an external PC.
Complete test setup, execution and reporting are handled locally from the touch screen.
Periodic VLF proof testing of shielded distribution cable insulation.
Confirming cable circuits and joints after installation or repair work.
Quality verification of new cable installations by contractors and utilities.
Substation bays, manholes and tunnels where a truck-mounted test set cannot reach.
Cable reliability and preventive-maintenance programs.
IEEE 400.2 recommends a test voltage related to the cable's phase-to-earth rating (U0), typically 1.5 to 3 times U0 depending on whether the test is acceptance or maintenance and on cable age. Confirm the target voltage for your specific cable class before testing.
DC testing can leave space charge in cross-linked (XLPE/EPR) insulation that may cause premature failure later. A sinusoidal VLF waveform reproduces the operating AC stress with polarity reversal each half cycle, giving a more realistic and safer test for polymer-insulated cables.
Yes. The 7-inch touch screen controls the full test sequence, interprets results against IEEE 400.2-2013 and prints them on the thermal printer, so no external PC is required in the field.
It is a two-piece split system — a 4 kg controller and a 20 kg high-voltage tank. Connect the two with the supplied HV lead and the return/earth lead, then program the test from the touch screen.