VLF-30

30 kV Very Low Frequency (VLF) AC Hipot Test Set

Lightweight two-piece 30 kV peak VLF hipot for routine and maintenance withstand testing of shielded power cables.

Maximum output voltage 0 – 30
Output current 0 – 30
Output frequencies 0.1 / 0.05 / 0.02 / 0.01
Load rating at 0.01 Hz ≤ 5.5
Measurement accuracy ± 3 % of reading
Controller + HV tank 4 + 20

Overview

Technical Specifications

Specification Value Unit
Output AC voltage (peak, sinusoidal) 0 – 30 kV
Output current (peak) 0 – 30 mA
Output frequency 0.1 / 0.05 / 0.02 / 0.01 Hz sinusoidal
Duty cycle Continuous
@ 0.1 Hz ≤ 0.5 µF
@ 0.05 Hz ≤ 1.1 µF
@ 0.02 Hz ≤ 2.2 µF
@ 0.01 Hz ≤ 5.5 µF
Measurement accuracy ± 3 % of reading
Voltage positive / negative peak error ≤ 3 %
Controller unit weight 4 kg
High-voltage tank (booster) weight 20 kg
Design Two-piece split system (controller + HV tank)
Power supply AC 220 V / AC 230 V, 50/60 Hz, or AC 120 V, 60 Hz
Operating temperature −10 … +50 °C
Storage temperature −20 … +70 °C
Humidity ≤ 85 % RH

Key Features

Compact split design for field mobility

Control unit of 4 kg plus a 30 kV high-voltage tank of 20 kg — one of the lightest split systems in the family, easily handled by two technicians.

True sinusoidal VLF waveform

Polarity reverses every half cycle like power-frequency AC, giving a space-charge-free stress appropriate for XLPE and EPR insulation.

Four output frequencies

0.1 / 0.05 / 0.02 / 0.01 Hz let the operator trade test time for reach on high-capacitance cable sections.

30 kV peak with 30 mA output

Delivers full rated voltage across the load rating up to 5.5 µF at 0.01 Hz on a continuous duty cycle.

Automatic IEEE 400.2-2013 interpretation

The 7-inch touch-screen controller judges results against IEEE 400.2 criteria automatically.

Built-in thermal printer & storage

Results are saved internally and printed on site, producing field documentation without an external PC.

No PC required

Complete test setup, execution and reporting are handled locally from the touch screen.

Applications

Routine & maintenance withstand testing

Periodic VLF proof testing of shielded distribution cable insulation.

Post-installation / post-repair verification

Confirming cable circuits and joints after installation or repair work.

Contractor handover checks

Quality verification of new cable installations by contractors and utilities.

Space-restricted sites

Substation bays, manholes and tunnels where a truck-mounted test set cannot reach.

Industrial & utility plants

Cable reliability and preventive-maintenance programs.

Frequently Asked Questions

What VLF test voltage should be applied to a cable under test?

IEEE 400.2 recommends a test voltage related to the cable's phase-to-earth rating (U0), typically 1.5 to 3 times U0 depending on whether the test is acceptance or maintenance and on cable age. Confirm the target voltage for your specific cable class before testing.

Why is a sinusoidal VLF test preferred over DC proof testing for XLPE/EPR cables?

DC testing can leave space charge in cross-linked (XLPE/EPR) insulation that may cause premature failure later. A sinusoidal VLF waveform reproduces the operating AC stress with polarity reversal each half cycle, giving a more realistic and safer test for polymer-insulated cables.

Can the VLF-30 be operated without a computer?

Yes. The 7-inch touch screen controls the full test sequence, interprets results against IEEE 400.2-2013 and prints them on the thermal printer, so no external PC is required in the field.

How is the VLF-30 transported and set up?

It is a two-piece split system — a 4 kg controller and a 20 kg high-voltage tank. Connect the two with the supplied HV lead and the return/earth lead, then program the test from the touch screen.