VLF-90
The VLF-90 is a 90 kV peak sinusoidal VLF hipot test set that brings the family's highest rating…
- Maximum output voltage 0 – 90
- Output current 0 – 30
- Output frequencies 0.1 / 0.05 / 0.02 / 0.01
60 kV Very Low Frequency (VLF) AC Hipot & Insulation Test Set
60 kV peak VLF hipot for medium/high-voltage shielded cables and rotating-machine insulation, with post-repair verification.
| Specification | Value | Unit |
|---|---|---|
| Output AC voltage (peak, sinusoidal) | 0 – 60 | kV |
| Output current (peak) | 0 – 30 | mA |
| Output frequency | 0.1 / 0.05 / 0.02 / 0.01 | Hz sinusoidal |
| Duty cycle | Continuous | |
| @ 0.1 Hz | ≤ 0.5 | µF |
| @ 0.05 Hz | ≤ 1.1 | µF |
| @ 0.02 Hz | ≤ 2.2 | µF |
| @ 0.01 Hz | ≤ 5.5 | µF |
| Measurement accuracy | ± 3 % of reading | |
| Voltage positive / negative peak error | ≤ 3 % | |
| Controller unit weight | 4 | kg |
| High-voltage tank (booster) weight | 50 | kg |
| Design | Two-piece split system (controller + HV tank) | |
| Power supply | AC 220 V / AC 230 V, 50/60 Hz, or AC 120 V, 60 Hz | |
| Operating temperature | −10 … +50 | °C |
| Storage temperature | −20 … +70 | °C |
| Humidity | ≤ 85 % RH | |
60 kV peak output for medium/high-voltage shielded cables and for motor and generator stator insulation testing.
Controlled VLF overvoltage makes serious defects fail during the test, where they can be found and corrected rather than later in service.
Low output frequencies keep charging current within rating on large capacitive machine windings while full test voltage is maintained.
Up to 5.5 µF at 0.01 Hz for long cable circuits and large windings.
Space-charge-free AC stress appropriate for XLPE/EPR insulation.
4 kg controller plus 50 kg high-voltage tank — high voltage reach without resonant-test-trailer weight.
IEEE 400.2-2013 pass/fail from the touch screen, stored internally and printed without a PC.
VLF withstand testing of medium- and high-voltage shielded power cables.
Verification of motor and generator stator insulation after installation or repair.
Re-testing cable circuits after joint repair or section replacement.
Routine VLF proof testing of industrial and utility cable circuits.
MV/HV cable and machine installations by contractors and utilities.
Yes. Rotating-machine windings are capacitive loads, and the very low output frequencies keep charging current within the set's 30 mA rating while the required test voltage is maintained. This makes the VLF-60 suitable for VLF insulation testing of motors and generators as well as shielded power cables.
If a cable or winding has a serious flaw, a controlled VLF overvoltage causes it to break down at the test site, where the fault can be located and repaired. The alternative risks an in-service failure at an unknown time and location.
It is designed for testing in accordance with IEEE 400.2-2013/2024 and IEC 60502-2, with automatic result interpretation per IEEE 400.2-2013.
It is a two-piece split system: a 4 kg controller and a 50 kg high-voltage tank, connected with the supplied high-voltage and return leads and operated from the touch screen without a PC.